|
Structured
Cabling Systems
Creative
Compromise -
Interior Layout of the Telecommunications Room by
Chuck Siebuhr
|
|
In
the November 1999 article, "Creative Compromise," I reviewed
an example design for an individual business tenant in a multifloor
commercial building. With all horizontal link distances being
well within distance limitations, the total office area is
served by one telecommunications room (TR). Understanding
that there is rarely a single solution, any number of alternatives
might have been considered, but there were certain physical
and cost constraints that had to be factored into the final
decision, hence the term "creative compromise."
Ideally,
the equipment could have been placed in one larger room, rather
than two smaller rooms. However, in this case, the ideal solution
was not an option. After carefully measuring and calculating
the overall usable square footage of the area to be served
and reviewing the client's minimum requirements, it was determined
that one work area outlet (WAO) would be required for every
62 square feet. (TIA standards recommend a basic minimum of
one WAO for every 100 square feet of usable floor space.)
In this
example, the space provided for equipment proved to be more
than adequate, even though segregated. In fact, the division
of space might be considered positive by many, since it provides
an unmistakable distinction between voice services and LAN/data
terminations.
|
|
"...there
is no single right way, but there are numerous wrong
ways. Only carefully conceived and executed plans will
survive the test of time, as well as the ever-increasing
demand for higher performance at lower long-term costs..."
|
|
| |
|
Future Proofing?
Realistically speaking, there is no sure way to future-proof
anything, but panels and patch cords could prove to be a forward-thinking
decision as technologies continue to evolve. Opinions will
vary, of course, as will individual site-specific requirements.
Again, there is no single right way, but there are numerous
wrong ways. Only carefully conceived and executed plans will
survive the test of time, as well as the ever-increasing demand
for higher performance at lower long-term costs.
Options,
Design Considerations and Cost
As is often the case, the system designer may offer options
that are declined by the client, usually because of concerns
over total cost. Reflecting this reality, the example presented
here is another example of compromise, but with the end-result
remaining the same as the original concept. The designer envisioned
terminating all horizontal cabling for voice lines on rack-mounted
patch panels and LAN/data lines on patch panels that were
inside equipment cabinets.
One reason
for proposing this approach for voice terminations is the
ease of administering MACs (moves, adds and changes) over
the life cycle of the system. MACS would require little more
than an appropriate patch cord and accurate record keeping.
In addition, it would pre-position every WAO to support LAN/data
service if required in the future. All too often, today's
voice outlet suddenly becomes tomorrow's data location. And
then there are also aesthetics to be considered. A carefully
configured rack of panels presents a more structured, neat
and orderly appearance than rings or troughs full of cross-connect
wire. Reduced long-term maintenance and administration cost
savings could easily offset the difference in initial installation
costs in a relatively short time, depending on the volume
and frequency of MACs.
In this
particular example (after much discussion), the client ultimately
focused on budgetary concerns and elected to reduce initial
costs by using a more familiar configuration for voice services,
such as punch down blocks and cross-connect jumpers. There
is nothing wrong with taking this approach for exclusively
voice systems at the present time. However, it seems obvious
that the rack, panel and patch cord concept would provide
more future flexibility and offer an embedded redundant infrastructure
in the event of any upgrades or technical surprises.
|
"Detailed
drawings are essential and if they are not furnished,
there will certainly be varying degrees of penalties
that can be traced back to assumptions. Carefully
prepared drawings can eliminate, or at least minimize
future problems."
|
|
TIA
recommendations presented in the suite of standards
(568A, 569A, 606 and 607) are incorporated into the
design as minimum acceptable requirements. Room 521
was selected for provisioning voice services, with Room
522 dedicated to LAN/data equipment. With the availability
of ample free wall space in Room 521, IDC (insulation
displacement connection) termination blocks were selected,
sized and spaced to accommodate reasonable future growth,
if required. In this case, the blocks could be any of
the industry accepted types commonly in use today (110,
KRONE, 66-type, etc.), since expansion or density is
not an issue.
Field
dimensions are verified and scaled onto the plan drawing,
along with corresponding width and height of backboards
to be mounted. Backboards are 3/4" AC grade void-free
plywood,
|
|
|
coated
with two coats of fire-retardant paint. Terminating blocks
and equipment fields are identified by colors that conform
with TIA recommendations. Detail drawings should represent
exact placement within room(s): width, height, cable pathway
and cross-connect routing paths, placement of power receptacles
(equipment or convenience) and any/all pertinent construction
notes. Indicate the points of the compass on the drawings,
with the top of the page as north.
In Room
521, two four-inch conduits are indicated in the northwest
corner of the room. One provides a pathway for the telco/LEC
from the building entrance facility (EF). The second is also
a pathway from the EF, but it is left vacant and capped for
future use. The location of the conduits takes advantage of
what would typically be unusable space just inside the doorway.
Drawings should indicate locations of fire extinguishers,
emergency lighting, internal WAOs, reserved (future) equipment
wall space or cabinet footprint/dimensions. Additional care
should be taken to provide unobstructed free workspace and
adequate room for door or panel openings. Include physical
properties to be considered, such as overhead ladder racks,
tray or conduit routes, suspended cable pathways, lighting
fixtures, paging speakers, sprinklers, security cameras and
sensors. HVAC requirements and dedicated equipment power outlets
should all be distinctively identified on all plans, prior
to any work activity being performed.
Detailed
drawings are essential and if they are not furnished, there
will certainly be varying degrees of penalties that can be
traced back to assumptions. Carefully prepared drawings can
eliminate, or at least minimize future problems.
|
|
Almost everyone
has access to a simple drawing program, if not a higher level
of CAD or perhaps VISIO, but even a clean hand-drawn copy
is better than nothing. Again, no detail is unimportant. It
doesn't require any special drafting abilities or formal construction
education to prepare a detailed working drawing. As long as
the plan is accurately dimensioned and includes all site-specific
information, it will serve admirably as a template to build
from. Clean as-builts can be prepared at the completion of
the project and updated as the need arises.
Some of the most important questions during the conceptual
design phase are deceptively simple:
- "Did
anything get overlooked?"
- "Will
everything fit in the allocated space?"
- "Is
the plan clear enough so some-one unfamiliar with the site
could interpret how and what must be done to satisfy the
intent of the proposal?
|
| [top
of page] [next
page] |
| |
Chuck
Siebuhr, RCDD, is senior technical editor for Cabling
Business Magazine and an instructor at Cabling Business
Institute. He has more than 30 years experience in the
telecommunications industry. Siebuhr is a founding member
of Association of Cabling Professionals (ACP), is a member
of BICSI, and is listed in National's Who's Who of Honored
Professionals and Executives, 1999-2000 edition.
|
|
|
 |